Modbus RTU decoder
✓ Valid frame · Request
| Field | Bytes | Value |
|---|---|---|
| slave | 01 | 1 |
| function | 03 | 3 Read Holding Registers |
| start | 00 00 | 0 (0x0000) |
| quantity | 00 0A | 10 |
| crc | C5 CD | 0xCDC5 = 0xCDC5 |
Model and assumptions
RTU frame: address, function, data, CRC-16 (reflected polynomial 0xA001, initial 0xFFFF, low byte first). The same function code has different lengths in request and response; automatic direction can be wrong for ambiguous frames. Addresses are zero-based; the 40001 notation is a device convention. Word order of 32-bit values depends on the device.
CRC: c=0xFFFF; c^=byte; 8×{ c = c&1 ? (c>>1)^0xA001 : c>>1 }
Waarvoor dit is
Die mees algemene veldkommunikasie-foute is 'n verkeerde CRC, 'n verkeerde adres, verwarrende woordorde en tyd-uit. Kopieer 'n raamwerk wat van 'n analiseerder of 'n seriële log is gekopieer om te sien watter veld verkeerd is, die toestandsuitskrif van die toestel en die waarskynlike interpretasies van registerwaardes.
Beperkings
Die gereedskap maak nie verbinding met toestelle of stuur data nie; elke berekening loop in jou browser. Modbus ASCII, Modbus TCP, CAN FD en J1939/CANopen ladingsinterpretasie is buite die scope. Automatiese rigting kan verkeerd wees vir ambiguouse raamwerke; kies dit handmatig.
Verwysings
Modbus oor Seriële Lyn V1.02 · Modbus-toepassingsprotokol V1.1b3 · ISO 11898-1:2015 (CAN data link layer) · CRC katalogus
Opleidingsmodel. Resultate is nie voldoende om 'n masjien te diagnoseer nie of veilige operasiegrense te stel nie.