Protocol inspector

Decode Modbus RTU, UART and CAN frames.

LOCAL CALCULATION · NO DEVICE CONNECTION

Modbus RTU decoder

✓ Valid frame · Request

FieldBytesValue
slave011
function033 Read Holding Registers
start00 000 (0x0000)
quantity00 0A10
crcC5 CD0xCDC5 = 0xCDC5
Model and assumptions

RTU frame: address, function, data, CRC-16 (reflected polynomial 0xA001, initial 0xFFFF, low byte first). The same function code has different lengths in request and response; automatic direction can be wrong for ambiguous frames. Addresses are zero-based; the 40001 notation is a device convention. Word order of 32-bit values depends on the device.

CRC: c=0xFFFF; c^=byte; 8×{ c = c&1 ? (c>>1)^0xA001 : c>>1 }

What it is for

The most common field communication faults are a wrong CRC, a wrong address, mixed-up word order and timeouts. Paste a frame copied from an analyser or a serial log to see which field is wrong, the device exception code and the likely interpretations of register values.

Limitations

The tool does not connect to devices or send data; every calculation runs in your browser. Modbus ASCII, Modbus TCP, CAN FD and J1939/CANopen payload interpretation are out of scope. Automatic direction can be wrong for ambiguous frames; choose it manually.

References

Modbus over Serial Line V1.02 · Modbus Application Protocol V1.1b3 · ISO 11898-1:2015 (CAN data link layer) · CRC catalogue

Educational model. Results are not sufficient to diagnose a machine or establish safe operating limits.