ROOTCASTLE / INŽENJERINGSKI LABORATORIJ
Inspektor protokola
Dekodiraj Modbus RTU, UART i CAN okviće.
LOCAL CALCULATION · NO DEVICE CONNECTION
Modbus RTU decoder
✓ Valid frame · Request
| Field | Bytes | Value |
|---|---|---|
| slave | 01 | 1 |
| function | 03 | 3 Read Holding Registers |
| start | 00 00 | 0 (0x0000) |
| quantity | 00 0A | 10 |
| crc | C5 CD | 0xCDC5 = 0xCDC5 |
Model and assumptions
RTU frame: address, function, data, CRC-16 (reflected polynomial 0xA001, initial 0xFFFF, low byte first). The same function code has different lengths in request and response; automatic direction can be wrong for ambiguous frames. Addresses are zero-based; the 40001 notation is a device convention. Word order of 32-bit values depends on the device.
CRC: c=0xFFFF; c^=byte; 8×{ c = c&1 ? (c>>1)^0xA001 : c>>1 }
Za što je to
Najčešći komunikacijski pogreške u polju su pogrešni CRC, pogrešna adresa, obrnut redoslov riječi i timeout-ovi. Kopirajte okvir iz analizatora ili serijalnog loga kako biste vidjeli koji polje nije ispravan, kod izuzetka i vjerojatne interpretacije vrijednosti registara.
Ograničenja
Alat se ne povezuje s uređajima ili šalje podatke; sva izračunavanja se odvijaju u vašem pregledniku. Interpretacija Modbus ASCII, Modbus TCP, CAN FD i J1939/CANopen payloada je izvan opsega. Automatski smjer može biti pogrešan za ambiguitetni okvi; odaberite ručno.
Reference
Modbus over Serial Line V1.02 · Modbus Application Protocol V1.1b3 · ISO 11898-1:2015 (CAN data link layer) · Popis CRC
Educational model. Rezultati nisu dovoljni za dijagnozu mašine ili postavljanje sigurnih granica rada.