Decodér Modbus RTU, UART og CAN frames.
LOCAL CALCULATION · NO DEVICE CONNECTION
Modbus RTU decoder
✓ Valid frame · Request
| Field | Bytes | Value |
|---|---|---|
| slave | 01 | 1 |
| function | 03 | 3 Read Holding Registers |
| start | 00 00 | 0 (0x0000) |
| quantity | 00 0A | 10 |
| crc | C5 CD | 0xCDC5 = 0xCDC5 |
Model and assumptions
RTU frame: address, function, data, CRC-16 (reflected polynomial 0xA001, initial 0xFFFF, low byte first). The same function code has different lengths in request and response; automatic direction can be wrong for ambiguous frames. Addresses are zero-based; the 40001 notation is a device convention. Word order of 32-bit values depends on the device.
CRC: c=0xFFFF; c^=byte; 8×{ c = c&1 ? (c>>1)^0xA001 : c>>1 }
Hvad er det til
De mest almindelige feltkommunikationsfejl er forkert CRC, forkert adresse, blandet ordrekkefølge og tidsudgange. Kopier en ramme fra en analysator eller en serie-log for at se, hvilket felt der er forkert, undtagen enhedsfejl-kode og sandsynlige fortolkninger af registerværdier.
Begrænsninger
Værktøjet tilslutter sig ikke enheder eller sender data; hver beregning kører i din browser. Modbus ASCII, Modbus TCP, CAN FD og J1939/CANopen payload-fortolkning er uden for omfang. Automatisk retning kan være forkert for tvetydige rammer; vælg den manuelt.
Referencer
Modbus over Serial Line V1.02 · Modbus Application Protocol V1.1b3 · ISO 11898-1:2015 (CAN data link layer) · CRC-katalog
Uddannelsesmodel. Resultaterne er ikke tilstrækkelige til at diagnosticere en maskine eller fastsikre sikre driftgrænser.