Inspector protokol
Decode Modbus RTU, UART dan CAN frames.
LOCAL CALCULATION · NO DEVICE CONNECTION
Modbus RTU decoder
✓ Valid frame · Request
| Field | Bytes | Value |
|---|---|---|
| slave | 01 | 1 |
| function | 03 | 3 Read Holding Registers |
| start | 00 00 | 0 (0x0000) |
| quantity | 00 0A | 10 |
| crc | C5 CD | 0xCDC5 = 0xCDC5 |
Model and assumptions
RTU frame: address, function, data, CRC-16 (reflected polynomial 0xA001, initial 0xFFFF, low byte first). The same function code has different lengths in request and response; automatic direction can be wrong for ambiguous frames. Addresses are zero-based; the 40001 notation is a device convention. Word order of 32-bit values depends on the device.
CRC: c=0xFFFF; c^=byte; 8×{ c = c&1 ? (c>>1)^0xA001 : c>>1 }
Untuk apa
Kesalahan komunikasi lapangan yang paling umum adalah CRC salah, alamat salah, urutan kata yang campur aduk, dan timeout. Tempel frame yang disalin dari analyzer atau log serial untuk melihat field mana yang salah, kode pengecualian perangkat, dan tafsir yang kemungkinan besar dari nilai register.
Kaslahan
Alat ini tidak terhubung ke perangkat atau mengirim data; setiap perhitungan berjalan di browser Anda. Interpretasi payload Modbus ASCII, Modbus TCP, CAN FD dan J1939/CANopen luar jangkauan. Arah otomatis bisa salah untuk frame yang ambigu; pilih secara manual.
References
Modbus over Serial Line V1.02 · Modbus Application Protocol V1.1b3 · ISO 11898-1:2015 (CAN data link layer) · Katalog CRC
Model pendidikan. Hasilnya tidak cukup untuk merusak mesin atau menetapkan batas operasi yang aman.