ROOTCASTLE / INŽENÝRSKÁ DÍLNA
Inspektor protokolů
Decode Modbus RTU, UART and CAN frames.
LOCAL CALCULATION · NO DEVICE CONNECTION
Modbus RTU decoder
✓ Valid frame · Request
| Field | Bytes | Value |
|---|---|---|
| slave | 01 | 1 |
| function | 03 | 3 Read Holding Registers |
| start | 00 00 | 0 (0x0000) |
| quantity | 00 0A | 10 |
| crc | C5 CD | 0xCDC5 = 0xCDC5 |
Model and assumptions
RTU frame: address, function, data, CRC-16 (reflected polynomial 0xA001, initial 0xFFFF, low byte first). The same function code has different lengths in request and response; automatic direction can be wrong for ambiguous frames. Addresses are zero-based; the 40001 notation is a device convention. Word order of 32-bit values depends on the device.
CRC: c=0xFFFF; c^=byte; 8×{ c = c&1 ? (c>>1)^0xA001 : c>>1 }
K čemu slouží
Nejčastější poruchy field communication jsou špatný CRC, špatná adresa, zamíchaný pořadí slov a časové přetékání. Vložte rámce skenované z analyzéru nebo serial log, abyste zjistili, který pole je špatné, kód výjimky zařízení a pravděpodobné interpretace hodnot registrů.
Omezení
Nástroj se nepřipojuje k zařízením a neposílá data; každý výpočet běží ve vašem prohlížeči. Interpretace payloadu Modbus ASCII, Modbus TCP, CAN FD a J1939/CANopen je mimo rozsah. Automatické směrování může být pro nejasné rámce špatné; zvolte ho ručně.
Referenční materiály
Modbus over Serial Line V1.02 · Modbus Application Protocol V1.1b3 · ISO 11898-1:2015 (CAN data link layer) · Seznam CRC
Educativní model. Výsledky nejsou dostatečné pro diagnostiku stroje nebo stanovení bezpečných provozních limitů.