Modbus RTU decoder
✓ Valid frame · Request
| Field | Bytes | Value |
|---|---|---|
| slave | 01 | 1 |
| function | 03 | 3 Read Holding Registers |
| start | 00 00 | 0 (0x0000) |
| quantity | 00 0A | 10 |
| crc | C5 CD | 0xCDC5 = 0xCDC5 |
Model and assumptions
RTU frame: address, function, data, CRC-16 (reflected polynomial 0xA001, initial 0xFFFF, low byte first). The same function code has different lengths in request and response; automatic direction can be wrong for ambiguous frames. Addresses are zero-based; the 40001 notation is a device convention. Word order of 32-bit values depends on the device.
CRC: c=0xFFFF; c^=byte; 8×{ c = c&1 ? (c>>1)^0xA001 : c>>1 }
Para que serve
Os fallos de comunicación de campo máis comunes son un CRC incorrecto, un enderezo incorrecto, orde de palabras mezclada e tempos de espera. Peche un marco copiado dun analizador ou un log serial para ver que campo está incorrecto, o código de excepción do dispositivo e as probables interpretacións dos valores dos registradores.
Limitações
A ferramenta non se conecta a dispositivos ou envía datos; calculeos atopan-se no seu navegador. Interpretação de payloads Modbus ASCII, Modbus TCP, CAN FD e J1939/CANopen está fora de ámbito. A dirección automática pode estar incorrecta para marcos ambíguos; escolla manualmente.
Referencias
Modbus over Serial Line V1.02 · Modbus Application Protocol V1.1b3 · ISO 11898-1:2015 (CAN data link layer) · Catálogo CRC
Modelo educativo. Os resultados non son suficientes para diagnosticar unha máquina ou establecer límites de operación seguros.