ROOTCASTLE / LABORATÓRIO DE ENGENHARIA
Inspetor de protocolo
Decodificar quadros Modbus RTU, UART e CAN.
LOCAL CALCULATION · NO DEVICE CONNECTION
Modbus RTU decoder
✓ Valid frame · Request
| Field | Bytes | Value |
|---|---|---|
| slave | 01 | 1 |
| function | 03 | 3 Read Holding Registers |
| start | 00 00 | 0 (0x0000) |
| quantity | 00 0A | 10 |
| crc | C5 CD | 0xCDC5 = 0xCDC5 |
Model and assumptions
RTU frame: address, function, data, CRC-16 (reflected polynomial 0xA001, initial 0xFFFF, low byte first). The same function code has different lengths in request and response; automatic direction can be wrong for ambiguous frames. Addresses are zero-based; the 40001 notation is a device convention. Word order of 32-bit values depends on the device.
CRC: c=0xFFFF; c^=byte; 8×{ c = c&1 ? (c>>1)^0xA001 : c>>1 }
Para que serve
Os erros de comunicação de campo mais comuns são um CRC incorreto, um endereço incorreto, ordem de palavras misturada e timeouts. Colete um quadro copiado de um analisador ou um log serial para ver qual campo está errado, o código de exceção do dispositivo e as prováveis interpretações dos valores dos registradores.
Limitações
A ferramenta não se conecta a dispositivos nem envia dados; todos os cálculos são executados no seu navegador. A interpretação de payload Modbus ASCII, Modbus TCP, CAN FD e J1939/CANopen está fora de escopo. A direção automática pode estar errada para quadros ambíguos; escolha-a manualmente.
Referências
Modbus sobre Linha Serial V1.02 · Protocolo de Aplicação Modbus V1.1b3 · ISO 11898-1:2015 (CAN data link layer) · Catálogo CRC
Modelo educacional. Os resultados não são suficientes para diagnosticar uma máquina ou estabelecer limites de operação seguros.